TA3105
Temperature transmitter
TA-025CLEM14-A-ZVG/US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — TA3105-00 — 30.09.2015 —
Product characteristics
Number of inputs and outputs
Number of analogue outputs: 1
Measuring range -50...150 °C -58...302 °F
Process connection
threaded connection G 1/4 external thread
Installation length EL [mm]
25
Application
Special feature
Gold-plated contacts
Measuring element
1 x Pt 1000; (to DIN EN 60751, class A)
Media
liquids and gases
Pressure rating [bar]
400
Electrical data
Operating voltage [V]
10...30 DC; ("supply class 2" to cULus)
Current consumption [mA]
< 30
Protection class
III
Reverse polarity protection
yes
Inputs / outputs
Number of inputs and outputs
Number of analogue outputs: 1
Outputs
Total number of outputs
1
Output signal
analogue signal
Number of analogue outputs
1
Analogue current output [mA]
4...20
Max. load [Ω]
(Ub - 8,5 V) / 21,5 mA; 24 V: 720 Ω
Short-circuit protection
yes
Overload protection
yes
Measuring/setting range
Measuring range -50...150 °C -58...302 °F
Resolution
Resolution of analogue
output
[K]
0.04
TA3105
Temperature transmitter
TA-025CLEM14-A-ZVG/US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — TA3105-00 — 30.09.2015 —
Accuracy / deviations
Precision analogue output [K]
± 0,3 + (± 0,1 % MS)
Temperature coefficient
[% of the span / 10 K]
0,1; (in case of deviation from the reference condition 25 ± 5 °C)
Response times
Dynamic response T05 / T09 [s]
1 / 3; (to DIN EN 60751)
Operating conditions
Ambient temperature [°C]
-40...100
Storage temperature [°C]
-40...100
Protection
IP 68; IP 69K
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance DIN EN 60068-2-6 20 g (10...2000 Hz)
MTTF [years]
1092
UL approval UL Approval no. K005
Mechanical data
Weight [g]
34
Dimensions [mm]
Ø 18.8
Materials
stainless steel (1.4404 / 316L); PEI; FKM
Materials (wetted parts)
stainless steel (1.4404 / 316L); FKM
Process connection
threaded connection G 1/4 external thread
Probe diameter [mm]
6
Installation length EL [mm]
25
Remarks
Remarks
The values for accuracy apply to flowing water.
referring to UL: for use on a low voltage circuit with overcurrent protection
in accordance with UL873 tab. 28.1 or Imax = 100/Ub (Ub = voltage of the circuit)
Pack quantity
1 pcs.
Electrical connection
Connector: 1 x M12; coding: A; Contacts: gold-plated
TA3105
Temperature transmitter
TA-025CLEM14-A-ZVG/US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — TA3105-00 — 30.09.2015 —
Connection
OUT: analogue output
colours to DIN EN 60947-5-2